NEMA ratings – enclosure classifications and types

NEMA 1: General purpose – intended for indoor use primarily to provide a degree of protection against contact with the enclosed parts in locations without unusual service conditions.

NEMA 2: Drip proof – intended for indoor use primarily to provide a degree of protection against limited amounts of falling water or dirt.

NEMA 3: Rain-tight, dust-tight, and sleet (ice) resistant – intended for outdoor use primarily to provide a degree of protection from wind-blown dust, rain, sleet, and undamaged by ice formation.

NEMA 3S: Rain-tight, dust-tight, and sleet (ice) resistant - intended for outdoor use primarily to provide a degree of protection against wind-blown dust, rain, sleet, and the external mechanism remains operable when ice-laden.

NEMA 3R: Rain-tight, dust-tight, and sleet (ice) resistant - intended for outdoor use primarily to provide a degree of protection against falling rain and sleet, undamaged by the formation of ice on the enclosure.

NEMA 4: Watertight and Dust-tight – intended for indoor/outdoor use to provide a degree of protection against splashing water, water seepage, falling or hose-directed water and severe external condensation, undamaged by the formation of ice on the enclosure.

NEMA 4X: Watertight and Dust tight, and corrosion resistant: - same as NEMA 4 with addition of corrosion resistance.

NEMA 6: Submersible – intended for indoor/outdoor use to provide a degree of protection against entry of water during submersion at a limited depth.

NEMA 6P: Submersible – same as a type 6 enclosure, but provides prolonged submersion protection at a limited depth.

NEMA 7: Explosion Proof (class I, division 1, A, B, C, D) designed to contain an internal explosion without causing an external hazard when installed in designated atmospheres and locations. Class I, Division 1 locations are those in which hazardous atmospheres may be present under normal operating conditions.

Group A = atmospheres containing acetylene.

Group B = atmospheres containing hydrogen.

Group C = atmospheres containing ethyl-ether vapors, ethylene, or cyclopropane.

Group D = atmospheres containing gasoline, hexane, naphtha, benzene, butane, propane, alcohol, acetone, benzol, lacquer, solvent vapors, and natural gas.

NEMA 9: Explosion Proof (class II, division 1, E, F, G,) – Dust-ignition-proof enclosures designed to prevent the entrance of dust and the enclosure devices do not produce sufficient heat to cause external surface temperatures capable of igniting dust on the enclosure or in the surrounding atmosphere. Class II, Division 1 locations are those in which combustible dust is, or maybe, present under normal conditions.

Title: NEMA ratings – enclosure classifications and types
Description: Enclosure Classifications and Types
Published: 1/4/2008
Last Edited: 1/17/2023

4 users found this article useful. Was this article useful to you?

Share

Information disclaimer:

The information contained in this article is for general information purposes only. The information is provided by United States Plastic Corp. and while we endeavor to keep the information up to date and correct, we make no representations or warranties of any kind, express or implied, about the completeness, accuracy, reliability, suitability or availability with respect to the website or the information, products, services, or related graphics contained on the website for any purpose. Any reliance you place on such information is therefore strictly at your own risk.